This is important for human comfort and for A/C system design.
Consider the "AIR" as a mixture of:
Temperature Range being studied (typically): -10 to +50 oC
Treat the DRY AIR as an IDEAL GAS with constant specific heat
CP = 1.005 kJ/kg-oK (use this for h = CPT or Dh = CPDT)
ALSO, we can treat the water vapor as an IDEAL GAS: P v = R T
Together, the dry air and the water vapor make a "mixture" where
P = Pa + Pv
FOR THE WATER VAPOR, evaluate enthalpy (h) using either:
A note on subscripts: a is for the dry air, v is for the water vapor
Specific humidity, w, (or absolute humidity) gives the measure of the water vapor in the air:
w = mv / ma (kg of H2O vapor/kg dry air)
using the ideal gas law: w = 0.622 ( Pv / Pa )
or: w = 0.622 [ Pv / ( P - Pv )]
Air can hold only a certain amount of water vapor. The limit is reached when Pv reaches the saturation pressure of water at the temperature of the mixture. The air is then saturated with moisture and is called SATURATED AIR.
Any moisture added to the saturated air will condense.
EXAMPLE:
Air at 25oC, 100 kPa
From Table A-4: PSAT@25 C = 3.169 kPa
IF: Pv = 0, we have dry air (no H2O vapor)
0< Pv < 3.169 kPa, we have unsaturated air
Pv = 3.169 kPa, we have saturated air
Relative Humidity, f, is a measure of amount of moisture in the air relative to the maximum amount it can hold at that temperature.
f = mv / mg (kg of H2O vapor/kg of H2O vapor in saturated air)
with Pg = PSAT@T, f = Pv / Pg
According to this definition: f will always be a number between 0 and 1 ( or we can write it as a percentage)
Absolute and relative humidity relations:

The enthalpy of the air is: h = ha + w hg (in kJ/kg of dry air)
EXAMPLE:
A 5m x 5m x 3m room contains air at 25oC and 100 kPa at a relative humidity of 75%. Determine:
(a) Pa = P - Pv Pv = f Pg = f PSAT@25 C = (0.75)(3.169 kPa) = 2.38 kPa
Pa = 100 kPa - 2.38 kPa = 97.62 kPa
(b) 
(c) h = ha + whv = CPT + whg from Table A-4: hg@25 C = 2547.2 kJ/kg
h = (1.005 kJ/kg-oC)(25oC) + (0.0152)(2547.2 kJ/kg)
h = 63.8 kJ/kg dry air
(d) Both the water vapor and dry air fill the room completely:
So, Va = Vv = VROOM
Then, using the ideal gas law:

Likewise, the mass of water vapor could be found:

OR, by using mv = wma = (0.0152)(85.61 kg) = 1.3 kg
If air is cooled at constant pressure, condensation begins at the dew point temperature: Tdp =T SAT@Pv
As air cools at constant pressure, the vapor pressure of the water, Pv remains constant. When the temperature drops to the saturation temperature for that pressure, condensation begins. Further cooling follows the saturated vapor line.
Procedure:
Compute the specific humidity of the saturated (wet bulb) air.
and P2 is the total (actual) pressure
Compute the specific humidity of the air around the dry bulb
Compute the relative humidity of the air around the dry bulb
Compute the enthalpy of the air per unit mass of dry air
h1 = ha1 + w1 hv1 = CPTDB + w1 hg@T-DB
EXAMPLE (Air at 1 atm. = 101.325 kPa):
Given: dry- and wet-bulb temperatures: TDB = 25oC, TWB = 15oC
Find: specific humidity (w), relative humidity (f), and enthalpy (h)
Procedure:
Compute the specific humidity of the saturated (wet bulb) air.
Compute the specific humidity of the air around the dry bulb
Compute the relative humidity of the air around the dry bulb
Compute the enthalpy of the air per unit mass of dry air
h1 = ha1 + w1 hv1 = CPTDB + w1 hg@T-DB
= (1.005 kJ/kg-oC)(25oC) + (0.00653)(2547.2 kJ/kg)
= 41.8 kJ/kg dry air

EXAMPLE:
Given the dry- and wet-bulb temperatures:
Find: the specific humidity (w), relative humidity (f), and enthalpy (h) from the psychrometric chart.
Read to the right margin, w= 6.5 g of H2O/kg of dry air
= 0.0065 kg of H2O/kg of dry air
Read from the curves of relative humidity, f = 33 %
Read from the upper left enthalpy scale, h = 42 kJ/kg of dry air
Read from the lines of specific volume, v = 0.853 m3/kg of dry air
Given any two of these properties, the others can be read from the chart.

AIR CONDITIONING

Most air conditioning systems can be treated as steady-flow processes.
For the dry air: ![]()
For the water vapor: ![]()
For the energy balance: ![]()
Outdoor air at 10oC, 1 atm. and 30% relative humidity flows into an air conditioning system at a rate of 45 m3/minute. The air is to be heated to 22oC. Determine the rate of heat supply required (in kW).
From the chart:
At the inlet, for a dry-bulb temperature of 10oC and fi = 30%
wi = 2.3 g H2O/kg dry air = 0.0023 kg H2O/kg dry air
hi = 16 kJ/kg dry air and vi = 0.805 m3/ kg dry air
At the exit:
Knowing we= wi and Te = 22oC, you follow the horizontal line of constant specific humidity until to reach a dry-bulb temperature of 22 oC and read, he = 28 kJ/kg dry air
then,
The same outdoor air as in the previous example (flowing into an air conditioning system at 45 m3/min.), after being heated to 22oC, is then humidified by an injection of hot steam to a final state of 25oC and 60% relative humidity. Find the mass flow rate of steam required.
The conservation of mass through this humidifying section is:
![]()
![]()
From the chart, at TDP = 25oC and f = 60%,
wout = 12 g H2O/kg dry air = 0.012 kg H2O/kg dry air
then, ![]()
Air enters a window A/C system at 1 atm., 30oC, 80 % relative humidity at a rate of 10 m3/min. The air leaves the A/C system as saturated air at 14oC. Also, part of the moisture which condensed during the process is removed at 14oC. Determine the rates of heat and moisture removal from the air.
The mass flow rate of dry air remains constant during the entire process.
The amount of moisture in the air decreases due to dehumidification (w3< w1 )
First, the air cools without condensation (w2= w1 )
Then, continues to cool, with condensation and f3= f2
For the dry air mass: ![]()
For the water mass: ![]()
![]()
The energy balance: ![]()
![]()
From the psychrometric chart:
- h1 = 85.4 kJ/kg dry air
- w1 = 0.0216 kg H2O/kg dry air
- v1 = 0.889 m3/kg dry air
- h3 = 39.3 kJ/kg dry air
- w3 = 0.010 kg H2O/kg dry air
From the saturated water table (Table A-4): hw = hf@14 C = 58.8 kJ/kg
Then, at the inlet: 
For the liquid water: ![]()
Energy balance: 